R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 1 / 6
R24 Compliance Computer
Paperless process recorder
Universal inputs
8–24
Recording channels
48
Full scan¹
100 ms
Internal recording
64 GB nominal
Supply¹
100–240 V AC / 24 V DC
¹ Scan at 24 inputs and supply variant conditions are specified in sections 02 and 05.
Assembled recorder
1
2
3
A FRONT / RIGHT
1 Panel bezel
2 Optically bonded touchscreen
3 Front USB Type-A
4
5
6
B REAR / EXAMPLE CONFIGURATION
4 Ventilation slots
5 Three plug-in input cards shown
6 Power and rear interfaces
USB Type-A exports recorder files. Ethernet and isolated RS-485 carry live process values.
Card quantity and type vary by order. Use the terminal schedule for the ordered unit.
Section index
02 Measurement inputs 03 Outputs and plant interfaces
04 Recording, display and software 05 Panel installation and supply
06 Specify your R24

Page 2

R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 2 / 6
Measurement inputs
8–24 universal inputs. Fitted input cards determine signal modes and measurement limits. At 24 inputs, the
nominal full-scan interval is 100 ms with sequential card polling.
Thermocouple conversion spans
Type Range (°C) Type Range (°C)
B 0 to 1,820 E −270 to 1,000
J −210 to 1,200 K −270 to 1,370
N −270 to 1,300 T −270 to 400
R −50 to 1,760 S −50 to 1,760
Type C: 0 to 2,310 °C software span. Specify the
sensor reference curve and required measurement
range when ordering.
RTD conversion ranges
Element Software span
(°C)
Software span
(Ω)
Pt100 −200 to 860 18.50–393.413
Pt1000 −200 to 860 185–3,934.13
jPt100 −100 to 500 59.57–284.02
Ni100 −100 to 420 74.25–248.66
Cu10 −100 to 260 5.12–19.11
2- or 3-wire input. Conversion spans describe software
scaling. Measurement limits and permissible error
depend on the input card and sensor.
Electrical signals
Signal Range or selection
DC millivolt ±20 mV, ±100 mV
DC voltage 0–1 V, ±1 V, 0–5 V, 1–5 V, 0–10 V, ±10 V, 0–20 V, ±20 V
DC current 0–5 mA, 0–20 mA, 4–20 mA
Frequency and binary Card-dependent. Specify level, frequency, duty cycle and quantity.
Measurement conditions
Parameter Reference value or condition
Reference conditions 23 ± 2 °C, 55 ± 10% RH, nominal supply, ≥30 min warm-up
Input impedance ≥10 MΩ for thermocouple and voltage ranges up to 1 V. ≥1 MΩ on higher voltage
ranges.
Current input burden ≤250 Ω at 20 mA
Cold-junction
compensation
Base-metal thermocouples: ±0.5 °C at 23 ± 2 °C and ±0.7 °C over 0–50 °C
RTD excitation and leads ≤1 mA for Pt100. 3-wire compensation for at least 10 Ω per matched lead.
Filtering Per channel: off, 50/60 Hz rejection or smoothing
Request the range-specific error limits for the selected card. Measurement inputs are for process signals only.
Direct connection to mains is prohibited.

Page 3

R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 3 / 6
Outputs and plant interfaces
Output configuration
Function Rating Conditions
Current outputs Up to 8. 0–20 or 4–20 mA. Fitted output card
External loop load 0–600 Ω at 20 mA ≥12 V compliance at minimum rated
supply
Output accuracy ±0.1% of 20 mA full scale (±20 μA) Reference conditions, selected output
card
Output timing 100 ms maximum update interval. ≤270 ms
10–90% step response.
Specified load
Relay contact form SPDT changeover, NO / COM / NC Fitted relay assembly
Resistive switching Up to 5 A at 250 V AC or 30 V DC Specify load type and inrush.
PID control Up to 8 simultaneous loops at 100 ms 8 fitted current outputs
Specify the combined input, current output and relay population with the order.
Physical interfaces
Port Technical data
Ethernet RJ45, 10/100BASE-TX, auto-negotiation
Serial Isolated 2-wire RS-485, 4,800–115,200 baud, switchable 120 Ω termination
USB USB Type-A host, USB 2.0 compatible. USB flash drive for recorder file export.
Plant protocols
Protocol Role
Modbus TCP Server over Ethernet, up to four clients.
Modbus RTU Responder on isolated RS-485.
Secure Modbus TCP TLS protection with certificate-based authentication.
OPC UA Read-only server for live process values.
DNP3 and PROFINET Protocol add-ons available on request.
Ethernet and RS-485 provide live process values for external logging. Export native recorder files via USB flash
drive. Wire the recorder using the terminal schedule for the ordered configuration.

Page 4

R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 4 / 6
Recording, display and software
Acquisition and storage
Function Technical data
Acquisition Sequential polling. 100 ms nominal full-scan interval at 24 fitted inputs (10 updates/s
per input).
Recording Up to 48 shared Float32 channels for measured and calculated values. 100 ms
recording interval (10 samples/s per recording channel).
Internal recording capacity 64 GB nominal.
Recorder file export Export native recorder files only to a USB flash drive via the USB Type-A host.
Retention Depends on channel count, recording interval, archive overhead and usable
capacity.
Raw payload at 48
Float32 channels
Per 24 h Per 365 days
100 ms recording
interval
165.89 MB 60.55 GB
1 s (calculation only) 16.59 MB 6.05 GB
These raw-sample figures use decimal units and exclude metadata, events, filesystem use and compression. Use
available storage and archive overhead for your retention calculation.
Display and batch operation
Function Technical data
Display Optically bonded 640 × 480 colour resistive touchscreen for glove or stylus use.
Review Live and historical trends, grouped views and on-panel review of measured or
calculated values. Eight configurable display groups.
Batch capture Start runs manually or from a configured Modbus coil or recording channel. Up to
eight equipment setups.
Batch review Find runs by lot identifier, batch number or date. Review their trends and export
data. Named local accounts identify operators who start or finish a manual run.
Alarms and calculations Four thresholds per channel with hysteresis and sample confirmation. Build
advanced alarm rules from calculated values.
Engineering models 26 model types for gas, flow, production and thermal calculations. 16 totalisers track
cumulative flow or consumption.
Companion software
Software Platform and function
Archive Viewer Windows. Opens native RDBF archive files, reviews trends and gaps, exports data
as CSV and produces CSV or PDF reports.
Recorder Configurator Windows. Prepares and validates compatible settings files offline.
For regulated applications, specify electronic records, signatures, audit and approval requirements.

Page 5

R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 5 / 6
Panel installation and supply
A
200.245 144.000
144.000
RIGHT SIDE FRONT REAR / EXAMPLE
A: BOPLA NGS-NK side clamp · Bare enclosure dimensions in mm
Mechanical and environmental data
Parameter Value or installation condition
CAD outline (W × H × D) 144 × 144 × 200.245 mm nominal. Allow additional space for connectors and cable
bends.
Mounting Indoor panel installation. Two BOPLA Uninorm NGS-NK screw clamps, order no.
37003000, one per side. Detail A shows the nominal fitted position.
Panel interface Detail A uses a 3 mm reference panel. Use the cutout dimensions for the ordered
configuration.
Cabinet installation Install the recorder in a protective industrial cabinet.
Operating conditions 0–50 °C at full population. 10–90% RH, non-condensing. Up to 2,000 m indoors.
Storage −20 to +60 °C unpowered, non-condensing
Installation category Pollution degree 2. AC supply overvoltage category II.
Power supply
Model Nominal supply Operating range
AC 100–240 V AC, 50/60 Hz. Class I protective
earth.
90–264 V AC, 47–63 Hz
DC 24 V DC, ordered separately. 19.2–28.8 V DC
Power budget: Allow 20 W for the recorder, including the USB load.
Technical documents
Download the signed EU Declaration of Conformity (AC and DC).
Use the R24 enclosure drawing to plan cabinet space. Request the panel cutout and terminal schedule for the
ordered configuration before machining or wiring.

Page 6

R24 / TECHNICAL DATA SHEET / EN
PITANT UG (haftungsbeschränkt) · R24-TDS-EN · V1.3 · 26 November 2026 6 / 6
Specify your R24
Specify the input, output and supply configuration together. The quotation confirms the fitted hardware and
ratings.
Selection Information for the quote
1. Supply Choose 100–240 V AC or 24 V DC. Include actual site voltage, cabinet grounding
and protection requirements.
2. Inputs Quantity by signal type, required ranges, RTD wiring and measurement error. Add
any frequency or binary inputs.
3. Outputs Number of analogue outputs and PID loops, connected loop resistance, relay load
type, AC or DC voltage, steady current and inrush.
4. Recording Number of values to record, recording interval, retention goal, batch triggers and
required CSV or PDF reports.
5. Plant integration Modbus TCP, Modbus RTU, Secure Modbus TCP or OPC UA. Include DNP3 or
PROFINET if required.
6. Installation Available panel depth and cutout, ambient conditions and required documents or
application-specific approvals. Attach the I/O list or a cabinet drawing if available.
7. Order details Quantity, delivery country, target delivery date and your company/contact details.
What the quote confirms
Quote item Scope
Configured instrument Supply version, fitted I/O, supported simultaneous population and protocol add-ons.
Installation package Panel cutout, terminal schedule, configuration limits and documents for the delivery
country.