R24 downloadsDownload PDF
R24 Modbus register map
PDF · EN · V1.2
Read-only Modbus TCP and RTU register map for firmware 1.2.36, source revision 63ce02b9.
Loading PDF preview…
Page 1
R24 / MODBUS REGISTER MAP / EN 01 / SCOPE AND ADDRESSING Modbus register map PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 1 / 4 Read live recorder pens and totalisers using function 04 (0x04), Read Input Registers. Modbus TCP and RTU use the same read-only process map. Firmware Source revision Map coverage 1.2.36 63ce02b9 384 input-register words Use this map with the firmware revision listed above. Before commissioning, match the recorder and client settings and read a known input over the selected transport. Transport setup On the recorder, open Setting → Modbus. Enable the required interface and match the client settings. Restart after changing the TCP port or either interface’s enable setting. Transport Client settings TCP Recorder IP address and configured port (factory 502). The direct connection example uses Unit ID 1. Plain Modbus TCP supports up to four client connections. RTU / RS-485 Factory 115200 bit/s, 8 data bits, no parity, 1 stop bit, address 1. Match the recorder’s baud, parity, stop bits and address (1 to 247). Input register blocks PDU offsets 3xxxx references Words Signal Type 0–95 30001–30096 96 Pen live value Float32 96–143 30097–30144 48 Pen scaled value Int16 144–239 30145–30240 96 Pen observed minimum Float32 240–335 30241–30336 96 Pen observed maximum Float32 336–367 30337–30368 32 Totaliser accumulator Float32 368–383 30369–30384 16 Totaliser status UInt16 Address the first value Use FC04, zero-based offset 0, count 2 for Pen 1. A client may ask for the one-based address (1) or the 3xxxx reference (30001). The reference equals 30001 + offset. Requests can read 1 to 125 consecutive words. Keep both Float32 words in the same request. This map covers input registers. FC04 diagnostics. 84 02 indicates an out-of-range request. 84 03 indicates an invalid count or truncated PDU. For no reply, check transport settings and the RTU address and wiring.
Page 2
R24 / MODBUS REGISTER MAP / EN 02 / PEN ADDRESSES / 1–24 Pen registers 1–24 PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 2 / 4 Tables show zero-based PDU start offsets. Float32 occupies two words and Int16 occupies one. Match the pen and its engineering unit to the recorder configuration. Pen Live Float32 Scaled Int16 Minimum Float32 Maximum Float32 1 0 96 144 240 2 2 97 146 242 3 4 98 148 244 4 6 99 150 246 5 8 100 152 248 6 10 101 154 250 7 12 102 156 252 8 14 103 158 254 9 16 104 160 256 10 18 105 162 258 11 20 106 164 260 12 22 107 166 262 13 24 108 168 264 14 26 109 170 266 15 28 110 172 268 16 30 111 174 270 17 32 112 176 272 18 34 113 178 274 19 36 114 180 276 20 38 115 182 278 21 40 116 184 280 22 42 117 186 282 23 44 118 188 284 24 46 119 190 286 Float32 byte order Each 16-bit word is most-significant-byte first. IEEE 754 Float32 is high-word first (ABCD). Combine (first word << 16) | second word and reinterpret the bits as Float32. The example words 0x422A and 0x8000 decode to 42.625. Example frames for Pen 1 Frame Request (hex) Synthetic response (hex) PDU 04 00 00 00 02 04 04 42 2A 80 00 TCP, Unit ID 1 00 01 00 00 00 06 01 04 00 00 00 02 00 01 00 00 00 07 01 04 04 42 2A 80 00 RTU, address 1 01 04 00 00 00 02 71 CB 01 04 04 42 2A 80 00 AF F4
Page 3
R24 / MODBUS REGISTER MAP / EN 03 / PEN ADDRESSES / 25–48 Pen registers 25–48 PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 3 / 4 The companion CSV lists decimal and hex offsets, input-register references, word counts, data types and encodings for each mapped value. Pen Live Float32 Scaled Int16 Minimum Float32 Maximum Float32 25 48 120 192 288 26 50 121 194 290 27 52 122 196 292 28 54 123 198 294 29 56 124 200 296 30 58 125 202 298 31 60 126 204 300 32 62 127 206 302 33 64 128 208 304 34 66 129 210 306 35 68 130 212 308 36 70 131 214 310 37 72 132 216 312 38 74 133 218 314 39 76 134 220 316 40 78 135 222 318 41 80 136 224 320 42 82 137 226 322 43 84 138 228 324 44 86 139 230 326 45 88 140 232 328 46 90 141 234 330 47 92 142 236 332 48 94 143 238 334 Scaled readings and value quality Interpret scaled words as signed Int16. The recorder rounds the live value × 10precision and clamps to −32768 through 32767. At precision 2, −1234 represents −12.34. Use Float32 to distinguish NaN or infinity from valid zero. All three encode as zero in the scaled table. Observed extrema are tracked since initialisation or reset. The uninitialised sentinels are +FLT_MAX (0x7F7FFFFF) for minimum and −FLT_MAX (0xFF7FFFFF) for maximum. There is no separate pen quality register.
Page 4
R24 / MODBUS REGISTER MAP / EN 04 / TOTALISER ADDRESSES AND STATUS Totaliser registers PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 4 / 4 Read FC04 at offset 336 (0x0150), count 48. The response contains 16 Float32 accumulators followed by 16 UInt16 status words. Totaliser Accumulator Float32 offset Status UInt16 offset 1 336 368 2 338 369 3 340 370 4 342 371 5 344 372 6 346 373 7 348 374 8 350 375 9 352 376 10 354 377 11 356 378 12 358 379 13 360 380 14 362 381 15 364 382 16 366 383 Status word Bits Mask Field Meaning 0 0x0001 Enabled 1 when the totaliser is enabled. 1 0x0002 Running 1 when active accumulation is reported. 2–3 0x000C Mode 0 continuous, 1 Logic 1 formula, 2 legacy digital gate, 3 reserved. 4–5 0x0030 Time base 0 per second, 1 per minute, 2 per hour, 3 per day. 6–11 0x0FC0 Source pen Zero-based. Add 1 for the on-screen number when bit 12 is set. 12 0x1000 Source in range 1 if the source index is below 48. 13 0x2000 Finite value 1 if the stored accumulator is neither NaN nor infinity. 14–15 0xC000 Reserved Ignore these bits. Example 0x3117 means enabled and running, Logic 1 formula, per-minute time base, and source Pen 5 in range with a finite accumulator. This firmware migrates legacy digital-gate settings to Logic 1 formula. A disabled totaliser can retain a stored value. Read Enabled, Running and Finite independently. Treat separate Modbus requests as separate observations.