Read-only Modbus TCP and RTU register map for firmware 1.2.36, source revision 63ce02b9.

Loading PDF preview…

Page 1

R24 / MODBUS REGISTER MAP / EN
01 / SCOPE AND ADDRESSING
Modbus register map
PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 1 / 4
Read live recorder pens and totalisers using function 04 (0x04), Read Input Registers. Modbus TCP and RTU use
the same read-only process map.
Firmware Source revision Map coverage
1.2.36 63ce02b9 384 input-register words
Use this map with the firmware revision listed above. Before commissioning, match the recorder and client
settings and read a known input over the selected transport.
Transport setup
On the recorder, open Setting → Modbus. Enable the required interface and match the client settings. Restart
after changing the TCP port or either interface’s enable setting.
Transport Client settings
TCP Recorder IP address and configured port (factory 502). The direct connection example uses
Unit ID 1. Plain Modbus TCP supports up to four client connections.
RTU / RS-485 Factory 115200 bit/s, 8 data bits, no parity, 1 stop bit, address 1. Match the recorder’s baud,
parity, stop bits and address (1 to 247).
Input register blocks
PDU offsets 3xxxx references Words Signal Type
0–95 30001–30096 96 Pen live value Float32
96–143 30097–30144 48 Pen scaled value Int16
144–239 30145–30240 96 Pen observed minimum Float32
240–335 30241–30336 96 Pen observed maximum Float32
336–367 30337–30368 32 Totaliser accumulator Float32
368–383 30369–30384 16 Totaliser status UInt16
Address the first value
Use FC04, zero-based offset 0, count 2 for Pen 1. A client may ask for the one-based address (1) or the 3xxxx
reference (30001). The reference equals 30001 + offset. Requests can read 1 to 125 consecutive words. Keep
both Float32 words in the same request. This map covers input registers.
FC04 diagnostics. 84 02 indicates an out-of-range request. 84 03 indicates an invalid count or truncated PDU.
For no reply, check transport settings and the RTU address and wiring.

Page 2

R24 / MODBUS REGISTER MAP / EN
02 / PEN ADDRESSES / 1–24
Pen registers 1–24
PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 2 / 4
Tables show zero-based PDU start offsets. Float32 occupies two words and Int16 occupies one. Match the pen
and its engineering unit to the recorder configuration.
Pen Live Float32 Scaled Int16 Minimum Float32 Maximum Float32
1 0 96 144 240
2 2 97 146 242
3 4 98 148 244
4 6 99 150 246
5 8 100 152 248
6 10 101 154 250
7 12 102 156 252
8 14 103 158 254
9 16 104 160 256
10 18 105 162 258
11 20 106 164 260
12 22 107 166 262
13 24 108 168 264
14 26 109 170 266
15 28 110 172 268
16 30 111 174 270
17 32 112 176 272
18 34 113 178 274
19 36 114 180 276
20 38 115 182 278
21 40 116 184 280
22 42 117 186 282
23 44 118 188 284
24 46 119 190 286
Float32 byte order
Each 16-bit word is most-significant-byte first. IEEE 754 Float32 is high-word first (ABCD). Combine (first word <<
16) | second word and reinterpret the bits as Float32. The example words 0x422A and 0x8000 decode to 42.625.
Example frames for Pen 1
Frame Request (hex) Synthetic response (hex)
PDU 04 00 00 00 02 04 04 42 2A 80 00
TCP, Unit ID 1 00 01 00 00 00 06 01 04 00 00 00 02 00 01 00 00 00 07 01 04 04 42 2A 80 00
RTU, address
1
01 04 00 00 00 02 71 CB 01 04 04 42 2A 80 00 AF F4

Page 3

R24 / MODBUS REGISTER MAP / EN
03 / PEN ADDRESSES / 25–48
Pen registers 25–48
PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 3 / 4
The companion CSV lists decimal and hex offsets, input-register references, word counts, data types and
encodings for each mapped value.
Pen Live Float32 Scaled Int16 Minimum Float32 Maximum Float32
25 48 120 192 288
26 50 121 194 290
27 52 122 196 292
28 54 123 198 294
29 56 124 200 296
30 58 125 202 298
31 60 126 204 300
32 62 127 206 302
33 64 128 208 304
34 66 129 210 306
35 68 130 212 308
36 70 131 214 310
37 72 132 216 312
38 74 133 218 314
39 76 134 220 316
40 78 135 222 318
41 80 136 224 320
42 82 137 226 322
43 84 138 228 324
44 86 139 230 326
45 88 140 232 328
46 90 141 234 330
47 92 142 236 332
48 94 143 238 334
Scaled readings and value quality
Interpret scaled words as signed Int16. The recorder rounds the live value × 10precision and clamps to −32768
through 32767. At precision 2, −1234 represents −12.34. Use Float32 to distinguish NaN or infinity from valid
zero. All three encode as zero in the scaled table.
Observed extrema are tracked since initialisation or reset. The uninitialised sentinels are +FLT_MAX
(0x7F7FFFFF) for minimum and −FLT_MAX (0xFF7FFFFF) for maximum. There is no separate pen quality
register.

Page 4

R24 / MODBUS REGISTER MAP / EN
04 / TOTALISER ADDRESSES AND STATUS
Totaliser registers
PITANT UG (haftungsbeschränkt) · R24-MODBUS-EN · V1.2 · 26 November 2026 · Technical reference 4 / 4
Read FC04 at offset 336 (0x0150), count 48. The response contains 16 Float32 accumulators followed by 16
UInt16 status words.
Totaliser Accumulator Float32 offset Status UInt16 offset
1 336 368
2 338 369
3 340 370
4 342 371
5 344 372
6 346 373
7 348 374
8 350 375
9 352 376
10 354 377
11 356 378
12 358 379
13 360 380
14 362 381
15 364 382
16 366 383
Status word
Bits Mask Field Meaning
0 0x0001 Enabled 1 when the totaliser is enabled.
1 0x0002 Running 1 when active accumulation is reported.
2–3 0x000C Mode 0 continuous, 1 Logic 1 formula, 2 legacy digital gate, 3
reserved.
4–5 0x0030 Time base 0 per second, 1 per minute, 2 per hour, 3 per day.
6–11 0x0FC0 Source pen Zero-based. Add 1 for the on-screen number when bit 12 is
set.
12 0x1000 Source in range 1 if the source index is below 48.
13 0x2000 Finite value 1 if the stored accumulator is neither NaN nor infinity.
14–15 0xC000 Reserved Ignore these bits.
Example 0x3117 means enabled and running, Logic 1 formula, per-minute time base, and source Pen 5 in range
with a finite accumulator. This firmware migrates legacy digital-gate settings to Logic 1 formula.
A disabled totaliser can retain a stored value. Read Enabled, Running and Finite independently. Treat separate
Modbus requests as separate observations.