map_revision,reviewed_source,signal_id,label,point_index,function_code,pdu_offset_decimal,pdu_offset_hex,input_register_reference,register_count,data_type,access,byte_order_within_word,value_encoding,unit,notes
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_01,Pen 1 live value,1,4,0,0x0000,30001,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_02,Pen 2 live value,2,4,2,0x0002,30003,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_03,Pen 3 live value,3,4,4,0x0004,30005,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_04,Pen 4 live value,4,4,6,0x0006,30007,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_05,Pen 5 live value,5,4,8,0x0008,30009,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_06,Pen 6 live value,6,4,10,0x000A,30011,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_07,Pen 7 live value,7,4,12,0x000C,30013,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_08,Pen 8 live value,8,4,14,0x000E,30015,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_09,Pen 9 live value,9,4,16,0x0010,30017,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_10,Pen 10 live value,10,4,18,0x0012,30019,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_11,Pen 11 live value,11,4,20,0x0014,30021,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_12,Pen 12 live value,12,4,22,0x0016,30023,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_13,Pen 13 live value,13,4,24,0x0018,30025,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_14,Pen 14 live value,14,4,26,0x001A,30027,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_15,Pen 15 live value,15,4,28,0x001C,30029,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_16,Pen 16 live value,16,4,30,0x001E,30031,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_17,Pen 17 live value,17,4,32,0x0020,30033,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_18,Pen 18 live value,18,4,34,0x0022,30035,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_19,Pen 19 live value,19,4,36,0x0024,30037,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_20,Pen 20 live value,20,4,38,0x0026,30039,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_21,Pen 21 live value,21,4,40,0x0028,30041,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_22,Pen 22 live value,22,4,42,0x002A,30043,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_23,Pen 23 live value,23,4,44,0x002C,30045,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_24,Pen 24 live value,24,4,46,0x002E,30047,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_25,Pen 25 live value,25,4,48,0x0030,30049,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_26,Pen 26 live value,26,4,50,0x0032,30051,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_27,Pen 27 live value,27,4,52,0x0034,30053,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_28,Pen 28 live value,28,4,54,0x0036,30055,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_29,Pen 29 live value,29,4,56,0x0038,30057,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_30,Pen 30 live value,30,4,58,0x003A,30059,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_31,Pen 31 live value,31,4,60,0x003C,30061,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_32,Pen 32 live value,32,4,62,0x003E,30063,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_33,Pen 33 live value,33,4,64,0x0040,30065,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_34,Pen 34 live value,34,4,66,0x0042,30067,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_35,Pen 35 live value,35,4,68,0x0044,30069,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_36,Pen 36 live value,36,4,70,0x0046,30071,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_37,Pen 37 live value,37,4,72,0x0048,30073,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_38,Pen 38 live value,38,4,74,0x004A,30075,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_39,Pen 39 live value,39,4,76,0x004C,30077,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_40,Pen 40 live value,40,4,78,0x004E,30079,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_41,Pen 41 live value,41,4,80,0x0050,30081,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_42,Pen 42 live value,42,4,82,0x0052,30083,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_43,Pen 43 live value,43,4,84,0x0054,30085,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_44,Pen 44 live value,44,4,86,0x0056,30087,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_45,Pen 45 live value,45,4,88,0x0058,30089,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_46,Pen 46 live value,46,4,90,0x005A,30091,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_47,Pen 47 live value,47,4,92,0x005C,30093,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_live_48,Pen 48 live value,48,4,94,0x005E,30095,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. Prefer for live acquisition.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_01,Pen 1 scaled value,1,4,96,0x0060,30097,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_02,Pen 2 scaled value,2,4,97,0x0061,30098,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_03,Pen 3 scaled value,3,4,98,0x0062,30099,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_04,Pen 4 scaled value,4,4,99,0x0063,30100,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_05,Pen 5 scaled value,5,4,100,0x0064,30101,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_06,Pen 6 scaled value,6,4,101,0x0065,30102,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_07,Pen 7 scaled value,7,4,102,0x0066,30103,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_08,Pen 8 scaled value,8,4,103,0x0067,30104,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_09,Pen 9 scaled value,9,4,104,0x0068,30105,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_10,Pen 10 scaled value,10,4,105,0x0069,30106,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_11,Pen 11 scaled value,11,4,106,0x006A,30107,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_12,Pen 12 scaled value,12,4,107,0x006B,30108,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_13,Pen 13 scaled value,13,4,108,0x006C,30109,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_14,Pen 14 scaled value,14,4,109,0x006D,30110,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_15,Pen 15 scaled value,15,4,110,0x006E,30111,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_16,Pen 16 scaled value,16,4,111,0x006F,30112,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_17,Pen 17 scaled value,17,4,112,0x0070,30113,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_18,Pen 18 scaled value,18,4,113,0x0071,30114,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_19,Pen 19 scaled value,19,4,114,0x0072,30115,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_20,Pen 20 scaled value,20,4,115,0x0073,30116,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_21,Pen 21 scaled value,21,4,116,0x0074,30117,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_22,Pen 22 scaled value,22,4,117,0x0075,30118,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_23,Pen 23 scaled value,23,4,118,0x0076,30119,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_24,Pen 24 scaled value,24,4,119,0x0077,30120,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_25,Pen 25 scaled value,25,4,120,0x0078,30121,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_26,Pen 26 scaled value,26,4,121,0x0079,30122,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_27,Pen 27 scaled value,27,4,122,0x007A,30123,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_28,Pen 28 scaled value,28,4,123,0x007B,30124,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_29,Pen 29 scaled value,29,4,124,0x007C,30125,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_30,Pen 30 scaled value,30,4,125,0x007D,30126,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_31,Pen 31 scaled value,31,4,126,0x007E,30127,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_32,Pen 32 scaled value,32,4,127,0x007F,30128,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_33,Pen 33 scaled value,33,4,128,0x0080,30129,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_34,Pen 34 scaled value,34,4,129,0x0081,30130,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_35,Pen 35 scaled value,35,4,130,0x0082,30131,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_36,Pen 36 scaled value,36,4,131,0x0083,30132,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_37,Pen 37 scaled value,37,4,132,0x0084,30133,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_38,Pen 38 scaled value,38,4,133,0x0085,30134,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_39,Pen 39 scaled value,39,4,134,0x0086,30135,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_40,Pen 40 scaled value,40,4,135,0x0087,30136,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_41,Pen 41 scaled value,41,4,136,0x0088,30137,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_42,Pen 42 scaled value,42,4,137,0x0089,30138,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_43,Pen 43 scaled value,43,4,138,0x008A,30139,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_44,Pen 44 scaled value,44,4,139,0x008B,30140,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_45,Pen 45 scaled value,45,4,140,0x008C,30141,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_46,Pen 46 scaled value,46,4,141,0x008D,30142,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_47,Pen 47 scaled value,47,4,142,0x008E,30143,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_scaled_48,Pen 48 scaled value,48,4,143,0x008F,30144,1,int16,read-only,MSB first,Signed two’s complement,Counts,Divide by 10^display_precision. Saturates at Int16 limits. Non-finite input encodes as zero.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_01,Pen 1 observed minimum,1,4,144,0x0090,30145,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_02,Pen 2 observed minimum,2,4,146,0x0092,30147,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_03,Pen 3 observed minimum,3,4,148,0x0094,30149,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_04,Pen 4 observed minimum,4,4,150,0x0096,30151,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_05,Pen 5 observed minimum,5,4,152,0x0098,30153,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_06,Pen 6 observed minimum,6,4,154,0x009A,30155,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_07,Pen 7 observed minimum,7,4,156,0x009C,30157,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_08,Pen 8 observed minimum,8,4,158,0x009E,30159,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_09,Pen 9 observed minimum,9,4,160,0x00A0,30161,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_10,Pen 10 observed minimum,10,4,162,0x00A2,30163,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_11,Pen 11 observed minimum,11,4,164,0x00A4,30165,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_12,Pen 12 observed minimum,12,4,166,0x00A6,30167,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_13,Pen 13 observed minimum,13,4,168,0x00A8,30169,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_14,Pen 14 observed minimum,14,4,170,0x00AA,30171,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_15,Pen 15 observed minimum,15,4,172,0x00AC,30173,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_16,Pen 16 observed minimum,16,4,174,0x00AE,30175,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_17,Pen 17 observed minimum,17,4,176,0x00B0,30177,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_18,Pen 18 observed minimum,18,4,178,0x00B2,30179,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_19,Pen 19 observed minimum,19,4,180,0x00B4,30181,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_20,Pen 20 observed minimum,20,4,182,0x00B6,30183,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_21,Pen 21 observed minimum,21,4,184,0x00B8,30185,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_22,Pen 22 observed minimum,22,4,186,0x00BA,30187,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_23,Pen 23 observed minimum,23,4,188,0x00BC,30189,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_24,Pen 24 observed minimum,24,4,190,0x00BE,30191,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_25,Pen 25 observed minimum,25,4,192,0x00C0,30193,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_26,Pen 26 observed minimum,26,4,194,0x00C2,30195,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_27,Pen 27 observed minimum,27,4,196,0x00C4,30197,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_28,Pen 28 observed minimum,28,4,198,0x00C6,30199,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_29,Pen 29 observed minimum,29,4,200,0x00C8,30201,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_30,Pen 30 observed minimum,30,4,202,0x00CA,30203,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_31,Pen 31 observed minimum,31,4,204,0x00CC,30205,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_32,Pen 32 observed minimum,32,4,206,0x00CE,30207,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_33,Pen 33 observed minimum,33,4,208,0x00D0,30209,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_34,Pen 34 observed minimum,34,4,210,0x00D2,30211,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_35,Pen 35 observed minimum,35,4,212,0x00D4,30213,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_36,Pen 36 observed minimum,36,4,214,0x00D6,30215,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_37,Pen 37 observed minimum,37,4,216,0x00D8,30217,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_38,Pen 38 observed minimum,38,4,218,0x00DA,30219,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_39,Pen 39 observed minimum,39,4,220,0x00DC,30221,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_40,Pen 40 observed minimum,40,4,222,0x00DE,30223,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_41,Pen 41 observed minimum,41,4,224,0x00E0,30225,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_42,Pen 42 observed minimum,42,4,226,0x00E2,30227,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_43,Pen 43 observed minimum,43,4,228,0x00E4,30229,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_44,Pen 44 observed minimum,44,4,230,0x00E6,30231,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_45,Pen 45 observed minimum,45,4,232,0x00E8,30233,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_46,Pen 46 observed minimum,46,4,234,0x00EA,30235,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_47,Pen 47 observed minimum,47,4,236,0x00EC,30237,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_min_48,Pen 48 observed minimum,48,4,238,0x00EE,30239,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. +FLT_MAX is the uninitialised minimum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_01,Pen 1 observed maximum,1,4,240,0x00F0,30241,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_02,Pen 2 observed maximum,2,4,242,0x00F2,30243,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_03,Pen 3 observed maximum,3,4,244,0x00F4,30245,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_04,Pen 4 observed maximum,4,4,246,0x00F6,30247,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_05,Pen 5 observed maximum,5,4,248,0x00F8,30249,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_06,Pen 6 observed maximum,6,4,250,0x00FA,30251,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_07,Pen 7 observed maximum,7,4,252,0x00FC,30253,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_08,Pen 8 observed maximum,8,4,254,0x00FE,30255,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_09,Pen 9 observed maximum,9,4,256,0x0100,30257,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_10,Pen 10 observed maximum,10,4,258,0x0102,30259,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_11,Pen 11 observed maximum,11,4,260,0x0104,30261,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_12,Pen 12 observed maximum,12,4,262,0x0106,30263,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_13,Pen 13 observed maximum,13,4,264,0x0108,30265,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_14,Pen 14 observed maximum,14,4,266,0x010A,30267,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_15,Pen 15 observed maximum,15,4,268,0x010C,30269,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_16,Pen 16 observed maximum,16,4,270,0x010E,30271,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_17,Pen 17 observed maximum,17,4,272,0x0110,30273,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_18,Pen 18 observed maximum,18,4,274,0x0112,30275,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_19,Pen 19 observed maximum,19,4,276,0x0114,30277,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_20,Pen 20 observed maximum,20,4,278,0x0116,30279,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_21,Pen 21 observed maximum,21,4,280,0x0118,30281,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_22,Pen 22 observed maximum,22,4,282,0x011A,30283,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_23,Pen 23 observed maximum,23,4,284,0x011C,30285,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_24,Pen 24 observed maximum,24,4,286,0x011E,30287,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_25,Pen 25 observed maximum,25,4,288,0x0120,30289,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_26,Pen 26 observed maximum,26,4,290,0x0122,30291,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_27,Pen 27 observed maximum,27,4,292,0x0124,30293,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_28,Pen 28 observed maximum,28,4,294,0x0126,30295,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_29,Pen 29 observed maximum,29,4,296,0x0128,30297,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_30,Pen 30 observed maximum,30,4,298,0x012A,30299,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_31,Pen 31 observed maximum,31,4,300,0x012C,30301,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_32,Pen 32 observed maximum,32,4,302,0x012E,30303,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_33,Pen 33 observed maximum,33,4,304,0x0130,30305,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_34,Pen 34 observed maximum,34,4,306,0x0132,30307,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_35,Pen 35 observed maximum,35,4,308,0x0134,30309,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_36,Pen 36 observed maximum,36,4,310,0x0136,30311,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_37,Pen 37 observed maximum,37,4,312,0x0138,30313,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_38,Pen 38 observed maximum,38,4,314,0x013A,30315,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_39,Pen 39 observed maximum,39,4,316,0x013C,30317,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_40,Pen 40 observed maximum,40,4,318,0x013E,30319,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_41,Pen 41 observed maximum,41,4,320,0x0140,30321,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_42,Pen 42 observed maximum,42,4,322,0x0142,30323,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_43,Pen 43 observed maximum,43,4,324,0x0144,30325,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_44,Pen 44 observed maximum,44,4,326,0x0146,30327,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_45,Pen 45 observed maximum,45,4,328,0x0148,30329,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_46,Pen 46 observed maximum,46,4,330,0x014A,30331,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_47,Pen 47 observed maximum,47,4,332,0x014C,30333,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),pen_max_48,Pen 48 observed maximum,48,4,334,0x014E,30335,2,float32,read-only,MSB first,ABCD,Configured pen engineering unit,IEEE 754. -FLT_MAX is the uninitialised maximum sentinel.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_01,Totaliser 1 accumulator,1,4,336,0x0150,30337,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_02,Totaliser 2 accumulator,2,4,338,0x0152,30339,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_03,Totaliser 3 accumulator,3,4,340,0x0154,30341,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_04,Totaliser 4 accumulator,4,4,342,0x0156,30343,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_05,Totaliser 5 accumulator,5,4,344,0x0158,30345,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_06,Totaliser 6 accumulator,6,4,346,0x015A,30347,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_07,Totaliser 7 accumulator,7,4,348,0x015C,30349,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_08,Totaliser 8 accumulator,8,4,350,0x015E,30351,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_09,Totaliser 9 accumulator,9,4,352,0x0160,30353,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_10,Totaliser 10 accumulator,10,4,354,0x0162,30355,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_11,Totaliser 11 accumulator,11,4,356,0x0164,30357,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_12,Totaliser 12 accumulator,12,4,358,0x0166,30359,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_13,Totaliser 13 accumulator,13,4,360,0x0168,30361,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_14,Totaliser 14 accumulator,14,4,362,0x016A,30363,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_15,Totaliser 15 accumulator,15,4,364,0x016C,30365,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_accumulator_16,Totaliser 16 accumulator,16,4,366,0x016E,30367,2,float32,read-only,MSB first,ABCD,Configured totaliser quantity,IEEE 754. Disabled totalisers can retain a stored value. Read the associated status.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_01,Totaliser 1 status,1,4,368,0x0170,30369,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_02,Totaliser 2 status,2,4,369,0x0171,30370,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_03,Totaliser 3 status,3,4,370,0x0172,30371,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_04,Totaliser 4 status,4,4,371,0x0173,30372,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_05,Totaliser 5 status,5,4,372,0x0174,30373,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_06,Totaliser 6 status,6,4,373,0x0175,30374,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_07,Totaliser 7 status,7,4,374,0x0176,30375,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_08,Totaliser 8 status,8,4,375,0x0177,30376,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_09,Totaliser 9 status,9,4,376,0x0178,30377,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_10,Totaliser 10 status,10,4,377,0x0179,30378,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_11,Totaliser 11 status,11,4,378,0x017A,30379,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_12,Totaliser 12 status,12,4,379,0x017B,30380,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_13,Totaliser 13 status,13,4,380,0x017C,30381,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_14,Totaliser 14 status,14,4,381,0x017D,30382,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_15,Totaliser 15 status,15,4,382,0x017E,30383,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.
V1.2,1.2.36 (63ce02b9ca417f90848aaa6eed4a509ea801260e),totaliser_status_16,Totaliser 16 status,16,4,383,0x017F,30384,1,uint16,read-only,MSB first,Bit 0 is least significant,Bit field,Decode using the status table in the register guide.